A VAV box sequence of operation can look like a wall of text, but underneath it is a simple idea: a map from zone temperature to airflow. Once you can picture that map, any sequence becomes readable. The three things to look for are the minimum airflow, the maximum airflow, and the deadband sitting between heating and cooling.
The Sequence as a Map From Temperature to Airflow
Imagine a graph with zone temperature along the bottom and airflow up the side. Two temperature setpoints, a heating setpoint and a cooling setpoint, divide the horizontal axis into three regions. Warmer than the cooling setpoint, the zone needs cooling. Cooler than the heating setpoint, it needs heat. In between, it needs nothing.
The box controller turns each region into a behavior. The temperature control loop produces an output, and the sequence maps that output onto an airflow setpoint. For a pressure independent box, the inner flow loop then positions the damper to hit that airflow, as covered in the previous article.
The Three Operating Modes
Cooling mode. When the zone temperature rises above the cooling setpoint, the airflow setpoint rises with it. The cooling loop output is mapped to an airflow setpoint that runs from the minimum up to the cooling maximum, and the maximum is reached once the zone is a certain distance above setpoint. In one published example, that happens about one degree above the cooling setpoint, though the proportional band is adjustable. The cooling maximum itself is selected for design cooling conditions.
Deadband mode. When the zone temperature sits between the cooling and heating setpoints, the box is satisfied. The airflow setpoint is the minimum airflow, no reheat is active, and the box is otherwise inactive until the zone drifts out of the band in either direction.
Heating mode. When the zone falls below the heating setpoint, the box adds heat. In the conventional single maximum sequence, the airflow stays at the same minimum while the reheat valve modulates to hold the zone temperature. In the dual maximum sequence, covered later in this series, the airflow rises from the minimum toward a separate heating maximum after the reheat coil reaches its capacity.
Where the Deadband Comes From
The deadband is simply the gap between the heating and cooling setpoints, and it is a design decision. One university guideline, for example, uses an occupied cooling setpoint of 74 degrees Fahrenheit and an occupied heating setpoint of 70, giving a four degree deadband, with unoccupied setpoints of 78 and 68 that widen the band when the space is empty. All of these values are adjustable.
The deadband matters because it prevents the system from fighting itself. Without a gap, a zone could be pushed into heating immediately after being cooled, wasting energy on reheat to undo cooling that was just provided. A wider deadband reduces that fighting, at the cost of allowing more temperature variation.
The Minimum Airflow Setpoint Does Three Jobs
The minimum airflow setpoint is the most consequential number in the sequence, and it is doing several jobs at once.
It delivers ventilation. The minimum airflow in the deadband is commonly selected to provide the zone's required ventilation. If the minimum is too low, the zone does not get its outdoor air.
It keeps the box controllable. The minimum has to be high enough that the box can measure and control airflow stably and accurately. Below a certain airflow, velocity sensors lose accuracy, and the control loop cannot reliably hold the setpoint.
It sets the reheat penalty. Every cubic foot of cooled air supplied at minimum airflow that is not needed for cooling must be reheated if the zone cools below setpoint. A high minimum airflow therefore wastes reheat energy.
Traditionally, the minimum has been set high, typically around thirty to fifty percent of the cooling maximum airflow, partly because the conventional single maximum sequence uses the minimum airflow in heating mode as well. A high minimum then leaves zones overcooled in the deadband and wastes reheat energy. Dual maximum sequences were developed to lower the minimum to around ten to twenty percent of maximum, a topic for a later article in the series.
The Maximum Airflow Setpoint
The cooling maximum is set at the airflow needed to meet the zone's design cooling load. It is the ceiling of the airflow range, and it determines how much supply air the system must be able to deliver when every zone is at peak. Setting it too low leaves the zone unable to meet its load on a hot day, and setting it too high wastes fan capacity and can make the box harder to control at the low end.
Occupied and Unoccupied Modes
Most sequences include different behavior for occupied and unoccupied periods. When the zone is unoccupied, the setpoints widen and the minimum airflow is often reduced, in some sequences all the way to zero, so the box supplies air only when temperatures drift far enough to require it. This saves fan and conditioning energy without affecting occupant comfort.
Reading a Sequence Critically
When reviewing a VAV box sequence, a few questions cut quickly to what matters:
What is the minimum airflow, and how was it chosen? Does it match the ventilation requirement, and is it high enough for the box to control accurately?
Does the sequence use a single maximum or a dual maximum? That decides whether heating mode airflow equals the deadband airflow.
How wide is the deadband, and does it change between occupied and unoccupied modes?
What happens at the boundaries? Where exactly does the airflow reach the cooling maximum, and what does reheat do when it reaches its limit?
The Practical Takeaway
A VAV box sequence is a map from zone temperature to airflow, divided into cooling, deadband, and heating regions. The minimum airflow, which serves ventilation, controllability, and reheat energy all at once, and the maximum airflow, which serves the design cooling load, define the range the box operates in. The deadband prevents cooling and heating from fighting each other. Reading a sequence well means understanding how these three elements interact, particularly the minimum, which is where most of the design tension sits.