Sensor Failure Fallback Logic: What Happens When an Economizer's Humidity Sensor Fails

esearch modeling a typical office building with assumed errors of about two degrees Fahrenheit for dry bulb sensors and about four percent relative humidity for humidity sensors reached a striking result.

Written byAryan Raj Pandey Updated October 16, 2026 English
Technical ArticleReading Content
Sensor Failure Fallback Logic: What Happens When an Economizer's Humidity Sensor Fails banner
Views
33
  • Enhance Knowledge
  • Knowledge Sharing
  • Resource Networking

Free to join — save articles and keep learning.

Aryan Raj Pandey
Aryan Raj Pandey

Who is this article actually for?

Perfect for

  • You work in HVAC
  • You're a Mechanical Engineering professional
  • You have 3+ years of hands-on experience in this field

Before you enrol

  • Advanced level — assumes working knowledge of Mechanical Engineering
New to Mechanical Engineering? Browse beginner courses →

Article details

An economizer makes its decisions from a handful of sensors, and sensors fail. Wires break, probes foul, and humidity elements slowly drift out of calibration. The useful question is not whether a sensor will eventually misbehave, but what the controller does when it happens. A well-designed sequence degrades gracefully, stepping down to a simpler strategy it can still trust. A poorly designed one either keeps making decisions from bad data or quietly stops saving energy.

Why Humidity Sensors Are the Weak Link

Temperature sensors are generally stable and accurate for long periods. Humidity sensors are not. Relative humidity elements are prone to calibration drift, even when new, and an enthalpy calculation inherits every bit of that error.

Research modeling a typical office building with assumed errors of about two degrees Fahrenheit for dry bulb sensors and about four percent relative humidity for humidity sensors reached a striking result. Once sensor error was included, a fixed dry bulb limit with a setpoint optimized for the climate was the best or nearly the best option in every climate, while differential enthalpy control landed at or near the worst. Fixed enthalpy combined with a fixed dry bulb limit also performed well, because the dry bulb limit buffers the enthalpy sensor's error. A differential enthalpy setup also needs two humidity sensors, one outdoors and one in the return air, so their tolerances stack. The effect varies by climate, but the lesson is consistent: the more a strategy depends on humidity measurements, the more it depends on sensors that are hardest to keep accurate.

Two Kinds of Failure

It helps to separate failures into two types, because the controller can only respond to one of them.

Hard failures are the obvious ones, such as a broken wire, a disconnected probe, or a reading that falls outside any physically possible range. The controller can detect these directly and switch logic.

Soft failures are drifted or biased readings that still look plausible. A humidity sensor reading five points too low appears to be working perfectly, so no fallback ever triggers. The only way to catch it is through diagnostics that look at outcomes rather than the sensor itself.

Energy standards address this second category through fault detection and diagnostics requirements. Addenda to the 2016 edition of ASHRAE 90.1 require economizer fault detection that can identify air temperature sensor faults, failure to economize when the unit should, economizing when it should not, dampers that do not modulate, and excess outdoor air, with faults reported to a fault management system. Those last symptoms are exactly what a drifting humidity sensor can produce. The same addenda set minimum accuracy requirements for sensors used in these controls, for example about plus or minus five percent relative humidity across the twenty to eighty percent range and about plus or minus three Btu per pound for enthalpy over its working range.

The Fallback Ladder

The general principle is to step down to the most capable strategy that the remaining healthy sensors can still support. Published controller designs describe several examples of how this works.

Outdoor humidity sensor fails, controller set for differential enthalpy. One design falls back to differential dry bulb control, while using the return air humidity reading to check that space humidity does not climb too high.

Outdoor humidity sensor fails, controller set for single enthalpy. The same design disables free cooling altogether, because without an outdoor humidity reading the possibility of bringing in damp air cannot be ruled out.

Return air humidity sensor fails, controller set for differential enthalpy. The decision drops to single enthalpy, using the outdoor sensor against a fixed limit.

Return air temperature sensor fails. Differential dry bulb becomes single dry bulb, and differential enthalpy becomes single enthalpy.

A different published logic describes a slightly different ladder. If the outdoor enthalpy sensor fails but the outdoor dry bulb sensor is healthy, the controller reverts to a dry bulb decision, comparing outdoor temperature to a setpoint. If the dry bulb sensor fails while the enthalpy sensor is healthy, the controller bypasses its dry bulb override and relies on enthalpy. If a damper position sensor fails, the system substitutes the damper command signal.

Two Philosophies for the Same Failure

Notice that two designs handle the same failure, loss of the outdoor humidity reading, in different ways. One reverts to dry bulb. The other turns the economizer off. Neither is wrong. They reflect different views of risk.

Failing open, continuing to economize on a simpler strategy, preserves energy savings but accepts some risk of bringing in humid air. Failing closed, disabling the economizer, is safe for comfort and coil loading but gives up free cooling until someone repairs the sensor. The right answer depends on climate. In a dry climate, falling back to dry bulb is relatively harmless, since cool air there is generally dry air. In a humid climate, the same fallback recreates the exact problem that made enthalpy control necessary in the first place, as discussed in the article on climate zone and economizer control. That is a good argument for failing closed in humid regions.

Making Fallbacks Visible

A fallback that silently takes over is a hidden degradation. The building keeps working, so no one complains, while the economizer quietly runs in a lesser mode for months. Good practice is to raise an alarm every time the controller drops to a fallback strategy and to make it visible in the building automation system, so a repair is scheduled instead of forgotten.

Commissioning is the other safeguard. A common practice is functional testing, deliberately disconnecting or overriding each sensor and confirming that the controller steps down as the sequence of operation says it should, and that the alarm appears. This is only possible if the sequence of operation actually states the fallback for each sensor, which brings up the most practical point of all.

What This Means for Design

Specify the fallback behavior explicitly, sensor by sensor, in the sequence of operation, instead of leaving it to a manufacturer's default. Choose a strategy whose fallback matches the climate. Consider adding a dry bulb limit to an enthalpy strategy so the temperature reading protects against humidity sensor error. And budget for sensor calibration on a schedule, since the cheapest sensor failure to deal with is the one that gets caught before it drifts.

The Practical Takeaway

When an economizer's humidity sensor fails, what matters is what the controller does next. Hard failures can trigger a stepdown to a simpler strategy, soft failures need diagnostics to catch, and the right fallback depends on whether the climate makes humid air or merely warm air the bigger risk. A design that spells out each fallback, alerts someone when it happens, and gets tested at commissioning keeps an economizer honest. One that leaves these questions open can look like it is working long after it has stopped helping.

EveryEng. For everyone in Engineering.

Article suitable for

Go deeper with a full course

Courses on the tools and skills this article covers.

Opportunities that await you!

Career opportunities

Free to read

Join EveryEng to save articles and keep learning

Why people choose EveryEng

Industry-aligned articles, expert knowledge, hands-on learning, and career-relevant topics — all in a flexible and supportive environment.

Put no limit on your engineering passion.

We would love to hear from you.

Engineers collaborating around a laptop